G1/AS1 Personal Hygiene

How many WC pans, urinals, basins, baths and showers a building needs by G1/AS1's Tables 1 to 4, and which must be accessible.

  • G1/AS12nd Edition Amendment 610 Oct 2011

Fixture count

Figure 1's method: the building's use and its people, unisex facilities or facilities for each sex, and Tables 1 to 4 read for the WC pans, urinals, basins, baths and showers it needs.

The building

Its people

Facilities

Key figures

WC pans
6
Table 1
Urinals
2
Table 1
Basins
4
Table 1
Accessible WCs
1
Table 1
Baths or showers
0
Table 2
  1. Each sex

    30 females and 48 males, from 60 occupants at Table 3's 0.5 and 0.8.

    Table 3

  2. Staff

    6 staff with facilities of their own, counted as staff facilities and added.

    Table 1 Note 5 a)

  3. Females

    WC pans: 3. Basins: 2.

    Table 1

  4. Males

    WC pans: 3. Urinals: 2. Basins: 2.

    1.1.3, Table 1

  5. Accessible

    Accessible WC pans: 1. Accessible basins: 1. They may be among those above.

    4.2.1, Table 1, Note 6 c)

  6. Baths and showers

    Baths or showers: 0.

    1.1.4, Table 2

  7. Accessible showers

    Where showers are provided, at least one accessible shower compartment.

    Table 2, Figure 8

Reset the fixture count?

The building's use, its people and its spaces go back to where they started. The answers on Requirements and the ticks on Show on drawings are kept.

Educational. Confirm with your building consent authority and the current documents. G1/AS1 2.1.1, 2.3.3 to 2.3.8, 3.4.2, 5.0.2 and 6.2.1: values stated in the paragraphs listed.