Durability and compatibility

The treatment each timber part of a house needs, the steel that fixes it in the site's exposure zone, and which materials may touch or drain onto each other.

  • B2/AS13rd Edition28 Jul 2025
  • Building Product Specifications1st Edition Amendment 12 Apr 2026
  • NZS 3602:2003
  • NZS 3604:2011
  • E2/AS14th Edition28 Jul 2025
  • DBH Timber Treatment (2007)

This site's exposure zone

Read from NZS 3604's map, Section 4.2. Chosen here, it is the project's, and every tool that reads the zone takes it.

Timber treatment and fixings

Each part of a timber-framed house: how long it has to last, the treatment its timber needs and the steel that fixes it.

Structural fixings, sheltered
Set the zone
NZS 3604:2011 Table 4.1
ShelteredExposed45°1234657810911121314Type 304 stainless1516H5H3.2H1.2H3.2

Treatment

  • H1.2 boron, dyed pink
  • H1.2 solvent-borne, dyed blue
  • H3.1 no added colour, or a green of its own
  • H3.2 · H4 · H5 copper, natural green-brown
Every row is a part of a timber-framed house to NZS 3604; the zone columns are NZS 3604 Section 4's.
#PartLastsTreatmentFixings, zones B and CFixings, zones D and E
1PilesIn the ground; fixed near it50 yrH5NZS 3602 Table 1, 1A.1
Connectors: 304 stainless steel
Nails and screws: 304 stainless or better
NZS 3604 Table 4.1, 4.4.4 (a), Table 4.3, Table 4.3 note (7)
Connectors: 304 stainless steel
Nails and screws: 304 stainless or better
NZS 3604 Table 4.1, 4.4.4 (a), Table 4.3, Table 4.3 note (7)
2Deck postsSet in the ground, carrying the deck50 yrH5NZS 3602 Table 1, 1A.4
Connectors: 304 stainless steel
Nails and screws: 304 stainless or better
NZS 3604 Table 4.1, 4.4.4 (a), Table 4.3, Table 4.3 note (7)
Connectors: 304 stainless steel
Nails and screws: 304 stainless or better
NZS 3604 Table 4.1, 4.4.4 (a), Table 4.3, Table 4.3 note (7)
3Bearers and joistsUnder the floor, out of the weather50 yrH1.2BPS Table 1C.1
Connectors: hot-dip galvanised where the subfloor vents 7000 mm² or less, 304 stainless steel where it vents more
Nails and screws: galvanised steel
NZS 3604 Table 4.1, Table 4.3
Connectors: 304 stainless steel
Nails and screws: galvanised steel
NZS 3604 Table 4.1, Table 4.3
4Ground floor boardsTimber flooring over the subfloor50 yrH1.2BPS Table 1C.3
Nails and screws: mild steel
NZS 3604 Table 4.3
Nails and screws: mild steel
NZS 3604 Table 4.3
5Exterior wallsClosed, inside the wall50 yrH1.2BPS Table 1D.14
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
6Internal wallsClosed50 yrH1.2BPS Table 1E.5
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
7Cavity battensIn the wall cavity50 yrH3.1BPS Table 1D.10
Held by the cladding's nails
E2/AS1 Table C.3.1.1 note (3)
Held by the cladding's nails
E2/AS1 Table C.3.1.1 note (3)
8Weatherboards, radiata pineExposed, painted15 yrH3.1NZS 3602 Table 2, 2A.1
Nails and screws: galvanised steel
NZS 3604 Table 4.3; E2/AS1 Table C.1.1.1A (6)
Nails and screws: galvanised steel, punched, puttied and painted
NZS 3604 Table 4.3; E2/AS1 Table C.1.1.1A (6)
9Upper floor joistsInside, under the upper room50 yrH1.2BPS Table 1E.2
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
10Upper floor boardsTimber flooring, inside50 yrH1.2BPS Table 1E.7
Nails and screws: mild steel
NZS 3604 Table 4.3
Nails and screws: mild steel
NZS 3604 Table 4.3
11Balcony joists, cantileveredUnder the enclosed balcony, past the wall below50 yrH3.2BPS Table 1D.7
Nail plates: hot-dip galvanised
Connectors: hot-dip galvanised
Nails and screws: hot-dip galvanised
NZS 3604 Table 4.1, 4.4.4 (b), Table 4.3
Nail plates: hot-dip galvanised
Connectors: hot-dip galvanised
Nails and screws: hot-dip galvanised
NZS 3604 Table 4.1, 4.4.4 (b), Table 4.3
12Parapet framingAround the balcony, within and beneath the parapet50 yrH1.2BPS Table 1D.5
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
13Skillion roof framingLined underneath, over the single storey50 yrH1.2BPS Table 1D.3
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
Nail plates: continuously coated galvanised
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.3
14Roof trusses and framingRoof space50 yrH1.2BPS Table 1E.1
Nail plates: continuously coated galvanised, Z275
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.2, Table 4.3
Nail plates: continuously coated galvanised, Z275
Connectors: mild steel
Nails and screws: mild steel
NZS 3604 Table 4.1, Table 4.2, Table 4.3
15Open deck bearers and joistsExposed, open deck50 yrH3.2NZS 3602 Table 1, 1B.3
Connectors: 304 stainless steel
Nails and screws: 304 stainless or better
NZS 3604 Table 4.1, 4.4.4 (a), Table 4.3
Connectors: 304 stainless steel
Nails and screws: 304 stainless or better
NZS 3604 Table 4.1, 4.4.4 (a), Table 4.3
16Decking boardsExposed, no roof over it15 yrH3.2NZS 3602 Table 2, 2A.7
Nails and screws: 304 stainless or better
NZS 3604 Table 4.3, 4.4.4 (a)
Nails and screws: 304 stainless or better
NZS 3604 Table 4.3, 4.4.4 (a)
  1. Sheltered or exposed Closed is inside the wall or roof; sheltered is open to salt air but kept out of the rain, above a 45° line down from the edge of a floor, deck or roof; exposed is below it, or out in the rain.

    NZS 3604:2011 Table 4.1 note (4), Figure 4.3

  2. Copper-treated timber Timber treated with copper, H3.2 and up, takes Type 304 stainless steel fixings wherever it is sheltered or exposed, in every zone.

    NZS 3604:2011 4.4.4

  3. Piles near the ground Fixings and nails into a pile within 600 mm of the ground are stainless steel.

    NZS 3604:2011 Table 4.1, Table 4.3 note (7)

  4. Type 304 or 316 Type 304 stainless steel meets the Building Code, though it can show surface rust. Type 316 goes beyond what the Code asks and is for where the look matters.

    NZS 3604:2011 Table 4.3 note (9)

  5. Flooring Plywood and particleboard flooring need no treatment. In a wet area where an impervious coating cannot be kept up, timber or plywood flooring is H3.1 at least.

    NZS 3602:2003 Table 1, 1C.3, 1E.7, note (7)

  6. Drained subfloor A subfloor holding steel fixings is drained so that it does not pond.

    NZS 3604:2011 4.4.1 (a)

Other parts

Parts of a house the drawing does not show, and the treatment each needs.

PartTreatmentLasts
Timber or plywood frame foundationsNZS 3602 Table 1, 1A.2H550 yr
Retaining wall uprightsNZS 3602 Table 1, 1A.6H550 yr
Retaining wall rails and boardsNZS 3602 Table 1, 1A.7H450 yr
Verandah posts above the ground, exposed rafters and beamsNZS 3602 Table 1, 1B.3H3.250 yr
Laminated beams out in the weatherNZS 3602 Table 1, 1B.1H350 yr
Laminated posts out in the weatherNZS 3602 Table 1, 1B.2H350 yr
Plywood cladding that bracesNZS 3602 Table 1, 1B.4H350 yr
Sarking and roof framing behind shingles or shakesBPS Table 1D.1H1.250 yr
Enclosed flat roof framingBPS Table 1D.2H1.250 yr
Wall framing within an enclosed balconyBPS Table 1D.6H1.250 yr
Plywood fascias, barges and cover boardsNZS 3602 Table 2, 2A.3H315 yr
Plywood sheet cladding that does not braceNZS 3602 Table 2, 2A.4H315 yr
Exterior joinery: window and door frames, sills and doorsNZS 3602 Table 2, 2A.5H315 yr
Flooring in a wet area whose coating cannot be kept upNZS 3602 Table 1 note (7)H3.150 yr

The rules behind it

B2/AS1 Durability→E2/AS1 External Moisture→

Per B2/AS1 Table C.1.1.1: Durability requirements of nominated building elements, pp.15–21; B2/AS1 2.1.1.1, Figure 2.1.1.2, 3.3.1.1 and 3.3.2.1: values stated in the paragraphs listed; Building Product Specifications 3.5.1.3 and Tables 1C, 1D, 1E and 2B; NZS 3602:2003 Tables 1 and 2, categories 1A, 1B and 2A, Table 1 note (7), and C105.1; NZS 3604:2011 Section 4.4, Tables 4.1 to 4.3 and 4.4.4; Appendix C Material tables, pp.181–189: Tables C.1.1.1A, C.1.1.1B, C.1.1.1C and C.3.1.1; Department of Building and Housing, Timber Treatment (2007), Identifying timber treatments and Branding.